Proportional-Integral-Derivative (PID) Controller

The IDAES framework contains a basic PID control implementation, which is described in this section.

Example

The following code demonstrated the creation of a PIDBlock, but for simplicity, it does not create a dynamic process model. A full example of a dynamic process with PID control is being prepared for the IDAES examples repository and will be referenced here once completed.

The valve opening is the controlled output variable and pressure “1” is the measured variable. The controller output for the valve opening is restricted to be between 0 and 1. The measured and output variables should be indexed only by time. Fortunately there is no need to create new variables if the variables are in a property block or not indexed only by time. Pyomo’s Reference objects can be use to create references to existing variables with the proper indexing as shown in the example.

The calculate_initial_integral option calculates the integral error in the first time step to match the initial controller output. This keeps the controller output from immediately jumping to a new value. Unless the initial integral error is known, this option should usually be True.

The controller should be added after the DAE expansion is done. There are several variables in the controller that are usually meant to be fixed; as shown in the example, they are gain, time_i, time_d, and setpoint. For more information about the variables, expressions, and parameters in the PIDBlock, model see Variables and Expressions.

from idaes.generic_models.control import PIDBlock, PIDForm
from idaes.core import FlowsheetBlock
import pyomo.environ as pyo

m = pyo.ConcreteModel(name="PID Example")
m.fs = FlowsheetBlock(default={"dynamic":True, "time_set":[0,10]})

m.fs.valve_opening = pyo.Var(m.fs.time, doc="Valve opening")
m.fs.pressure = pyo.Var(m.fs.time, [1,2], doc="Pressure in unit 1 and 2")

pyo.TransformationFactory('dae.finite_difference').apply_to(
    m.fs,
    nfe=10,
    wrt=m.fs.time,
    scheme='BACKWARD',
)

m.fs.measured_variable = pyo.Reference(m.fs.pressure[:,1])

m.fs.ctrl = PIDBlock(
    default={
        "pv":m.fs.measured_variable,
        "output":m.fs.valve_opening,
        "upper":1.0,
        "lower":0.0,
        "calculate_initial_integral":True,
        "pid_form":PIDForm.velocity,
    }
)

m.fs.ctrl.gain.fix(1e-6)
m.fs.ctrl.time_i.fix(0.1)
m.fs.ctrl.time_d.fix(0.1)
m.fs.ctrl.setpoint.fix(3e5)

Controller Windup

The current PID controller model has no integral windup prevention. This will be added to the model in the near future.

Class Documentation

class idaes.generic_models.control.pid_controller.PIDBlock(*args, **kwargs)

This is a PID controller block. The PID Controller block must be added after the DAE transformation.

Args:

rule (function): A rule function or None. Default rule calls build(). concrete (bool): If True, make this a toplevel model. Default - False. ctype (str): Pyomo ctype of the block. Default - “Block” default (dict): Default ProcessBlockData config

Keys
pv

A Pyomo Var, Expression, or Reference for the measured process variable. Should be indexed by time.

output

A Pyomo Var, Expression, or Reference for the controlled process variable. Should be indexed by time.

upper

The upper limit for the controller output, default=1

lower

The lower limit for the controller output, default=0

calculate_initial_integral

Calculate the initial integral term value if true, otherwise provide a variable err_i0, which can be fixed, default=True

pid_form

Velocity or standard form

initialize (dict): ProcessBlockData config for individual elements. Keys

are BlockData indexes and values are dictionaries described under the “default” argument above.

idx_map (function): Function to take the index of a BlockData element and

return the index in the initialize dict from which to read arguments. This can be provided to overide the default behavior of matching the BlockData index exactly to the index in initialize.

Returns:

(PIDBlock) New instance

class idaes.generic_models.control.pid_controller.PIDBlockData(component)[source]
build()[source]

Build the PID block

Variables and Expressions

Symbol

Name in Model

Description

\(v_{sp}(t)\)

setpoint[t]

Setpoint variable (usually fixed)

\(v_{mv}(t)\)

pv[t]

Measured process variable reference

\(u(t)\)

output[t]

Controller output variable reference

\(K_p(t)\)

gain[t]

Controller gain (usually fixed)

\(T_i(t)\)

time_i[t]

Integral time (usually fixed)

\(T_d(t)\)

time_d[t]

Derivative time (usually fixed)

\(e(t)\)

err[t]

Error expression (setpoint - pv)

err_d[t]

Derivative error expression

err_i[t]

Integral error expression (standard form)

err_d0

Initial derivative error value (fixed)

\(e_{integral}(0)\)

err_i0

Initial integral error value (fixed)

err_i_end

Last initial integral error expression

limits["h"]

Upper limit of output parameter

limits["l"]

Lower limit of output parameter

smooth_eps

Smooth min/max parameter

Formulation

There are two forms of the PID controller equation. The standard formulation can result in equations with very large summations. In the velocity form of the equation the controller output can be calculated based only on the previous state.

The two forms of the equations are equivalent, but the choice of form will affect robustness and solution time. It is not necessarily clear that the velocity form of the equation is always more numerically favorable, however it would usually be the default choice. Both forms are provided in case the standard form works better in some situations.

Standard Formulation

The PID controller equations are given by the following equations

\[e(t) = v_{sp}(t) - v_{mv}(t)\]
\[u(t) = K_p \left[ e(t) + \frac{1}{T_i} \int_0^t e(s) \text{d}s + T_d \frac{\text{d}e(t)}{\text{d}t} \right]\]

The PID equation now must be discretized.

\[u(t_i) = K_p \left[ e(t_i) + \frac{e_{integral}(0)}{T_i} + \frac{1}{T_i} \sum_{j=0}^{i-1} \Delta t_j \frac{e(t_j) + e(t_{j+1})}{2} + T_d \frac{e(t_i) - e(t_{i-1})}{\Delta t_{i-1}} \right]\]

Velocity Formulation

The velocity formulation of the PID equation may also be useful. The way the equations are written in the PID model, the integral term is a summation expression and as time increases the integral term will build up an increasing number of terms potentially becoming very large. This potentially has two affects, increasing round off error and computation time. The velocity formulation allows the controller output to be calculated based on the previous output.

First the usual PID controller equation can be rearranged to solve for the integral error.

\[\frac{1}{T_i} \int_0^t e(s) \text{d}s = \frac{u(t)}{K_p} - e(t) - T_d \frac{\text{d}e(t)}{\text{d}t}\]

The PID equation for some time (\(t + \Delta t\)) is

\[u(t + \Delta t) = K_p \left[ e(t + \Delta t) + \frac{1}{T_i} \int_0^{t+\Delta t} e(s) \text{d}s + T_d \frac{\text{d}e(t+\Delta t)}{\text{d}t} \right]\]
\[u(t + \Delta t) = K_p \left[ e(t + \Delta t) + \frac{1}{T_i} \int_t^{t+\Delta t} e(s) \text{d}s + \frac{1}{T_i} \int_0^{t} e(s) \text{d}s + T_d \frac{\text{d}e(t+\Delta t)}{\text{d}t} \right]\]
\[u(t + \Delta t) = u(t) + K_p \left[ e(t + \Delta t) - e(t) + \frac{1}{T_i} \int_t^{t+\Delta t} e(s) \text{d}s + T_d \left( \frac{\text{d}e(t+\Delta t)}{\text{d}t} - \frac{\text{d}e(t)}{\text{d}t}\right) \right]\]

Now we can discretize the equation using the trapezoid rule for the integral.

\[u(t + \Delta t) = u(t) + K_p \left[ e(t + \Delta t) - e(t) + \frac{\Delta t}{T_i} \left(\frac{e(t+\Delta t) + e(t)}{2} \right) + T_d \left( \frac{\text{d}e(t+\Delta t)}{\text{d}t} - \frac{\text{d}e(t)}{\text{d}t}\right) \right]\]

Since the derivative error term will require the error at the previous time step to calculate, this form will still result in a large summation being formed since in the model there is no derivative error variable. To avoid this problem, the derivative error term can equivalently be replaced with the derivative of the negative measured process variable.

\[u(t + \Delta t) = u(t) + K_p \left[ e(t + \Delta t) - e(t) + \frac{\Delta t}{T_i} \left(\frac{e(t+\Delta t) + e(t)}{2} \right)+ T_d \left( \frac{\text{d}v_{mv}(t+\Delta t)}{\text{d}t} - \frac{\text{d}v_{mv}(t)}{\text{d}t}\right) \right]\]

Now the velocity form of the PID controller equation can be calculated at each time point from just the state at the previous time point.

Substitution

In both the proportional and integral terms, error can be replaced with the negative measured process variable yielding equivalent results. This substitution is provided by the PID class and is done by default.

Output Limits

Smooth min and smooth max expressions are used to keep the controller output between a minimum and maximum value.